ANALYSIS OF FORCED OUTAGES -  ATPS CHACHAI   2009-10
APRIL
S.N. DETAILS DATE OF SHUTDOWN DATE OF SYNCHRONISATION PERIOD IN HOURS MU  LOST REASON CORRECTIVE ACTION TAKEN
  PLANNED
3 UNIT-3     0.00 0.00    
4 UNIT-4     0.00 0.00    
  FORCED
3 UNIT-3 28.04.09 28.04.09 8.20 1.00 Fire caught in Turbine Rear Fire Extingushed & Unit restarted.
4 UNIT-4 01.04.09 03.04.09 43.40 5.24 Tube Leakage in Cage Bypass Tube Leakage Attended & Unit restarted
03.04.09 03.04.09 2.08 0.26 Drum Level Low Drum level maintained & unit restarted
  TOTAL     53.68 6.50    
 
MAY
S.N. DETAILS DATE OF SHUTDOWN DATE OF SYNCHRONISATION PERIOD IN HOURS MU  LOST REASON CORRECTIVE ACTION TAKEN
  PLANNED
3 UNIT-3     0.00 0.00    
4 UNIT-4     0.00 0.00    
  FORCED
3 UNIT-3 15.05.09 15.05.09 6.52 0.82 Loss of Excitation Fault attended & Unit restarted
22.05.09 24.05.09 43.50 5.26 Boiler Tube Leakage Tube Leakage Attended & Unit restarted
4 UNIT-4 15.05.09 17.05.09 31.25 3.77 Minor fire in cable insulation caused short circuit of cable Fire extingushed,cable attended & Unit restarted
  TOTAL     81.27 9.85    
JUNE
S.N. DETAILS DATE OF SHUTDOWN DATE OF SYNCHRONISATION PERIOD IN HOURS MU  LOST REASON CORRECTIVE ACTION TAKEN
  PLANNED
3 UNIT-3     0.00 0.00    
4 UNIT-4     0.00 0.00    
  FORCED
3 UNIT-3 11.06.09 12.06.09 6.25 0.77 Electrical Fault Fault attended & Unit restarted
12.06.09 12.06.09 1.25 0.17 Electrical Fault Fault attended & Unit restarted
12.06.09 15.06.09 83.20 10.00 Electrical Fault Fault attended & Unit restarted
16.06.09 18.06.09 34.40 4.16 Economiser Tube Leakage Tube Leakage Attended & Unit restarted
4 UNIT-4 06.06.09 07.06.09 31.15 3.75 Minor fire in cable insulation caused short circuit of cable Fire extingushed,cable attended & Unit restarted
  TOTAL     156.25 18.85